配电装置输出

the electrical power from a device that allocates power to and serves information technology (IT) equipment. Power distribution unit (PDU) output does not include efficiency losses of any transformation that occurs within the PDU, but it can include downstream non-IT ancillary devices installed in IT racks, such as fans. If the PDU system supports non-IT equipment (e.g., computer room air-conditioning units, computer room air handlers, in-row coolers), this equipment must be metered and subtracted from the PDU output reading. The metering approach should be consistent with the metering required for the power usage efficiency (PUE) category (e.g., continuous consumption metering for PUE categories 1, 2, and 3). 

来自为信息技术 (IT) 设备分配电能以及为其服务的设备的电能。 配电装置 (PDU) 输出不包括 PDU 中任何转换的效率损失,但可以包括安装在 IT 机架中的下游非 IT 辅助设备,如风扇。 如果 PDU 系统支持非 IT 设备(如,计算机房空调装置、计算机房空气处理装置、行级制冷器),必须计量该设备的用电量并从 PDU 输出读数中减去。 计量方法应与用电效率 (PUE) 类别要求的计量方法一致(如,PUE 类别 1、2 和 3 的连续消耗计量)。